HOME -> Condensing unit -> MCU | 3 to 15 hp | +5 to -40 °C

 

  MCU series Condensing Unit

 


  >  +5 °C to -40 °C

  >  3 to 15 HP
  >  R 22 / R 404A
  >  Air cooled condenser
  >  Bitzer semi - hermetic compressor


The MCU series is available in models for medium temperature application and medium cooling capacities.


Compressor, condenser and receiver are fully piped and preassembled. It comes with receiver, filter drier, pressure switch, solenoid valve, electrical box, pressure gauge. Other selectable spare parts are on request for customization.


MCU-1.png


Technical Data and Dimension

 

Model
Q’ty
of Fan
Max. Air Flow
Condenser
Max. Fan
Power
Suction Line
Size
Liquid Line
Size
Dimension
L
B
H
D
E
m3 / h
W
inch
inch
mm
mm
mm
mm
mm
  MCU-3M   2   2 x 1800   2 x 120   3/4   3/8   1010   710   520   960   420
  MCU-4M   2   2 x 3000   2 x 120   3/4   3/8   1010   710   570   960   420
  MCU-5M   2   2 x 3000   2 x 120   1   1/2   1010   710   570   960   420
  MCU-8M   2   2 x 4500   2 x 180   1-1/8   5/8   1230   800   780   1180   520
  MCU-10M   2   2 x 4500   2 x 180   1-1/8   5/8   1430   900   880   1390   600
  MCU-15M   2   2 x 8720   2 x 600   1-3/8   5/8   1430   900   1080   1390   600
  MCU-2L   1   1 x 1800   1 x 120   7/8   3/8   600   700   520   550   420
  MCU-3L   2   2 x 1800   2 x 120   7/8   3/8   1010   710   520   960   420
  MCU-4L   2   2 x 3000   2 x 120   1-1/8   3/8   1010   710   570   960   420
  MCU-10L   2   2 x 4500   2 x 180   1-3/8   5/8   1430   900   880   1390   600
  MCU-15L   2   2 x 8720   2 x 600   1-3/8   5/8   1430   900   1080   1390   600

配图.png

 

Cooling Performance

For R 22

 

Model
Cooling Capacity, kW
Power Consumption, kW
Evaporation Temp. ºC
Evaporation Temp. ºC
-5
-10
-15
-25
-35
-5
-10
-15
-25
-35
  Medium Temperature: +5 ºC to -20 ºC
  MCU-3M   5.66   4.20   3.46   -   -   3.04   2.55   2.50   -   -
  MCU-4M   7.12   5.24   4.28   -   -   3.64   2.76   2.90   -   -
  MCU-5M   9.34   7.12   5.91   -   -   4.60   3.57   3.81   -   -
  MCU-8M   13.2   9.98   8.16   -   -   6.06   4.59   4.80   -   -
  MCU-10M   18.9   14.5   12.1   -   -   9.24   7.07   7.58   -   -
  MCU-15M   27.6   21.1   19.9   -   -   11.9   10.1   9.68   -   -
  Low Temperature: -5 ºC to -40 ºC
  MCU-2L   -   -   3.05   2.96   1.12   -   -   1.93   2.09   1.21
  MCU-3L   -   -   4.42   3.63   1.73   -   -   2.59   2.43   1.67
  MCU-4L   -   -   6.57   4.80   3.52   -   -   3.62   2.90   2.95
  MCU-10L   -   -   14.5   8.94   7.16   -   -   7.70   6.35   6.33
  MCU-15L   -   -   19.5   12.5   9.90   -   -   10.5   8.52   8.59

 

For R 404A

 

Model
Cooling Capacity, kW
Power Consumption, kW
Evaporation Temp. ºC
Evaporation Temp. ºC
-5
-10
-15
-25
-35
-5
-10
-15
-25
-35
  Low Temperature: -5 ºC to -40 ºC
  MCU-2L   -   -   -   2.83   16.5   -   -   -   2.07   1.49
  MCU-3L   -   -   5.69   3.80   2.26   -   -   3.40   2.69   2.02
  MCU-4L   -   -   6.81   4.58   2.75   -   -   4.17   3.21   2.40
  MCU-10L   -   -   16.3   10.7   6.37   -   -   8.61   6.87   5.20
  MCU-15L   -   -   20.0   13.7   8.48   -   -   11.9   9.19   6.94
  >  Cooling performance data is based on ambient temperature of 32 ºC



Customized Solution


We believe that a customized condensing unit with suitable components can make your job easier.

 

Based on our high - efficient heat exchange platform, we offer customers a wide range of reliable, branded components in order to design and produce the perfect customization solution.

 

MCU-2.png

MCU-3.png